WireFormula
NEC Table 310.16

400 kcmil Wire Ampacity

400 kcmil copper carries 280 A at 60 °C, 335 A at 75 °C, and 380 A at 90 °C. Aluminum carries 270 A at 75 °C. These are base values for three or fewer current-carrying conductors at 30 °C ambient.

Copper at 60 °C
280A
NM-B, TW
Copper at 75 °C
335A
THWN, RHW
Copper at 90 °C
380A
THHN, XHHW-2
Ampacity calculator
NEC Table 310.16

°C in the raceway or cable run

In the same raceway or cable

Base values assume 30 °C ambient and no more than three current-carrying conductors.
Result
No adjustment applied
Base ampacity (75 °C)
25A
Ambient correction
100%
Table 310.15(B)(1)
Bundle adjustment
100%
Table 310.15(C)(1)
Usable ampacity
25A
Adjusted: 25 A

12 AWG copper at 75 °C starts at 25 A. After corrections it carries 25 A, and the 25 A value is what you may use for overcurrent sizing when terminals are rated 75 °C.

400 kcmil ampacity by material

The same metal at the same size changes ampacity with insulation. The table below is the base Table 310.16 value — before ambient correction, before bundling adjustment, and before the terminal limit in 110.14(C).

Material60 °C75 °C90 °C
Copper280335380
Aluminum225270305

NEC 2023 Table 310.16, amperes, three or fewer current-carrying conductors at 30 °C ambient.

Applying corrections to 400 kcmil

Two factors reduce the number above. The first is ambient temperature: Table 310.15(B)(1) multiplies the base value by a factor from 1.22 at 10 °C down to 0.41 at 80 °C. The second is conductor count: Table 310.15(C)(1) applies 0.80 for four to six current-carrying conductors, 0.70 for seven to nine, and 0.50 for ten to twenty.

After both, 110.14(C) may cap the result at the termination temperature. If your breaker is rated 75 °C, 400 kcmil copper is a 75 °C conductor for the purpose of sizing the overcurrent device, no matter what the insulation says. The calculator above reports the base value, both factors, and the final usable ampacity side by side.

Ampacity alone does not determine the conductor you install. The wire size calculator adds the breaker selection and the equipment grounding conductor, and the voltage drop calculator tells you whether a long run needs a larger size anyway.

Common questions

How many amps can 400 kcmil copper wire carry?

280 A at 60 °C, 335 A at 75 °C, and 380 A at 90 °C, assuming no more than three current-carrying conductors and a 30 °C ambient. Higher ambient temperatures and bundled conductors reduce those values.

What breaker size for 400 kcmil copper?

Up to 335 A at 75 °C, or the next standard size above it under 240.4(B) if the ampacity falls between standard ratings and the breaker does not exceed 800 A.

What is 400 kcmil used for?

Larger conductors are typically feeders, subpanels, and service entrance conductors. The exact ampacity depends on insulation type, termination rating, ambient temperature, and how many current-carrying conductors share the raceway.