900 kcmil Wire Ampacity
900 kcmil copper carries 435 A at 60 °C, 520 A at 75 °C, and 585 A at 90 °C. Aluminum carries 425 A at 75 °C. These are base values for three or fewer current-carrying conductors at 30 °C ambient.
°C in the raceway or cable run
In the same raceway or cable
12 AWG copper at 75 °C starts at 25 A. After corrections it carries 25 A, and the 25 A value is what you may use for overcurrent sizing when terminals are rated 75 °C.
900 kcmil ampacity by material
The same metal at the same size changes ampacity with insulation. The table below is the base Table 310.16 value — before ambient correction, before bundling adjustment, and before the terminal limit in 110.14(C).
| Material | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| Copper | 435 | 520 | 585 |
| Aluminum | 355 | 425 | 480 |
NEC 2023 Table 310.16, amperes, three or fewer current-carrying conductors at 30 °C ambient.
Applying corrections to 900 kcmil
Two factors reduce the number above. The first is ambient temperature: Table 310.15(B)(1) multiplies the base value by a factor from 1.22 at 10 °C down to 0.41 at 80 °C. The second is conductor count: Table 310.15(C)(1) applies 0.80 for four to six current-carrying conductors, 0.70 for seven to nine, and 0.50 for ten to twenty.
After both, 110.14(C) may cap the result at the termination temperature. If your breaker is rated 75 °C, 900 kcmil copper is a 75 °C conductor for the purpose of sizing the overcurrent device, no matter what the insulation says. The calculator above reports the base value, both factors, and the final usable ampacity side by side.
Ampacity alone does not determine the conductor you install. The wire size calculator adds the breaker selection and the equipment grounding conductor, and the voltage drop calculator tells you whether a long run needs a larger size anyway.
Common questions
How many amps can 900 kcmil copper wire carry?
435 A at 60 °C, 520 A at 75 °C, and 585 A at 90 °C, assuming no more than three current-carrying conductors and a 30 °C ambient. Higher ambient temperatures and bundled conductors reduce those values.
What breaker size for 900 kcmil copper?
Up to 520 A at 75 °C, or the next standard size above it under 240.4(B) if the ampacity falls between standard ratings and the breaker does not exceed 800 A.
What is 900 kcmil used for?
Larger conductors are typically feeders, subpanels, and service entrance conductors. The exact ampacity depends on insulation type, termination rating, ambient temperature, and how many current-carrying conductors share the raceway.