NEC Table 310.16

What Size Wire for 25 Amps?

For a 25 amp circuit, the code minimum is 10 AWG copper for NM-B cable, 10 AWG copper for THHN with 75 °C terminations, or 10 AWG aluminum. The standard breaker is 25 A and the equipment grounding conductor is 10 AWG copper.

NM-B cable (60 °C)
10 AWG
Romex, residential branch circuits
THHN in conduit (75 °C)
10 AWG
Terminals rated 75 °C
Aluminum (75 °C)
10 AWG
Feeders and service conductors
Wire size calculator
NEC 310.16 · 240.4

Amps the circuit will carry

°C

Result
Sized per NEC 310.16
Minimum wire size
10 AWG
Copper · 30 A ampacity · 25 A breaker
Required ampacity
25A
Load as entered
Breaker size
25A
Table 240.6(A)
Equipment ground
10 AWG
Table 250.122
Insulation base
10 AWG
30 A at 60 °C
  • 240.4(D): 10 AWG copper is limited to 30 A overcurrent protection.

Why 25 amps lands on that conductor

The answer is not a single lookup. A 25 A circuit needs a conductor whose ampacity is at least the breaker rating after temperature correction and bundling adjustment. At 60 °C, 25 A falls between 10 AWG and the size below it, which is why 10 AWG is the minimum for cable.

Switch to THHN in conduit with 75 °C terminals and the same circuit often needs one size less, because the higher insulation and termination rating raise the ampacity of every size. That is a real saving in copper, and it is why the wire type selector matters more than the load number.

A 25 A continuous load — an EV charger, a water heater, a commercial lighting circuit — is different again. Section 210.20(A) makes you take 125% of the load before choosing the breaker, so the circuit behaves like a larger one. Use the calculator above with the continuous checkbox rather than reading a single row off a table.

Table 310.16 ampacities that matter here

SizeCopper 60 °CCopper 75 °CAluminum 75 °C
14 AWG1520—
12 AWG202520
10 AWG303530
8 AWG405040
6 AWG556550
4 AWG708565
3 AWG8510075
2 AWG9511590
1 AWG110130100
1/0 AWG125150120
2/0 AWG145175135
3/0 AWG165200155
4/0 AWG195230180

NEC 2023 Table 310.16, amperes, three or fewer current-carrying conductors at 30 °C ambient.

Before you buy wire

Three things can move the answer: the termination temperature on your actual breaker, the ambient temperature where the conductors run, and voltage drop on a long circuit. Check all three with the wire size calculator and the voltage drop calculator. If the load is a motor or an air conditioner, Article 430 or 440 governs and the conductor may be smaller than this page suggests.

Common questions

What size breaker do I need for 25 amps?

A 25 A breaker is the standard rating at or above 25 A in Table 240.6(A). If the load is continuous, the 125% rule may push you to the next standard size, so a 25 A continuous load can require a larger breaker than 25 A.

What size wire for 25 amps at 100 feet?

Ampacity does not change with distance, so the minimum stays 10 AWG copper for NM-B. Distance affects voltage drop: past roughly 75 feet at 120 V you may want to go up one size. Run the numbers in the voltage drop calculator before you buy wire.

Can I use aluminum wire for 25 amps?

Yes, at 10 AWG for 75 °C terminations. Aluminum is two sizes behind copper at these currents and is common for feeders and service conductors, but it needs terminals listed for aluminum and an antioxidant where the manufacturer requires it.