What Size Wire for 300 Amps?
For a 300 amp circuit, the code minimum is 350 kcmil copper for NM-B cable, 250 kcmil copper for THHN with 75 °C terminations, or 350 kcmil aluminum. The standard breaker is 300 A and the equipment grounding conductor is 4 AWG copper.
Amps the circuit will carry
°C
- 240.4(B): 350 AWG has 260.0 A ampacity, so the next standard breaker size (300 A) is permitted.
Why 300 amps lands on that conductor
The answer is not a single lookup. A 300 A circuit needs a conductor whose ampacity is at least the breaker rating after temperature correction and bundling adjustment. At 60 °C, 300 A falls between 350 kcmil and the size below it, which is why 350 kcmil is the minimum for cable.
Switch to THHN in conduit with 75 °C terminals and the same circuit often needs one size less, because the higher insulation and termination rating raise the ampacity of every size. That is a real saving in copper, and it is why the wire type selector matters more than the load number.
A 300 A continuous load — an EV charger, a water heater, a commercial lighting circuit — is different again. Section 210.20(A) makes you take 125% of the load before choosing the breaker, so the circuit behaves like a larger one. Use the calculator above with the continuous checkbox rather than reading a single row off a table.
Table 310.16 ampacities that matter here
| Size | Copper 60 °C | Copper 75 °C | Aluminum 75 °C |
|---|---|---|---|
| 14 AWG | 15 | 20 | — |
| 12 AWG | 20 | 25 | 20 |
| 10 AWG | 30 | 35 | 30 |
| 8 AWG | 40 | 50 | 40 |
| 6 AWG | 55 | 65 | 50 |
| 4 AWG | 70 | 85 | 65 |
| 3 AWG | 85 | 100 | 75 |
| 2 AWG | 95 | 115 | 90 |
| 1 AWG | 110 | 130 | 100 |
| 1/0 AWG | 125 | 150 | 120 |
| 2/0 AWG | 145 | 175 | 135 |
| 3/0 AWG | 165 | 200 | 155 |
| 4/0 AWG | 195 | 230 | 180 |
NEC 2023 Table 310.16, amperes, three or fewer current-carrying conductors at 30 °C ambient.
Before you buy wire
Three things can move the answer: the termination temperature on your actual breaker, the ambient temperature where the conductors run, and voltage drop on a long circuit. Check all three with the wire size calculator and the voltage drop calculator. If the load is a motor or an air conditioner, Article 430 or 440 governs and the conductor may be smaller than this page suggests.
Common questions
What size breaker do I need for 300 amps?
A 300 A breaker is the standard rating at or above 300 A in Table 240.6(A). If the load is continuous, the 125% rule may push you to the next standard size, so a 300 A continuous load can require a larger breaker than 300 A.
What size wire for 300 amps at 100 feet?
Ampacity does not change with distance, so the minimum stays 350 kcmil copper for NM-B. Distance affects voltage drop: past roughly 50 feet at 120 V you may want to go up one size. Run the numbers in the voltage drop calculator before you buy wire.
Can I use aluminum wire for 300 amps?
Yes, at 350 kcmil for 75 °C terminations. Aluminum is two sizes behind copper at these currents and is common for feeders and service conductors, but it needs terminals listed for aluminum and an antioxidant where the manufacturer requires it.
